Type/Code: TM131-5L927/101
Brand/Manufacturer: Endress+Hauser
Description: iTHERM ModuLine TM131
Custom Description: ĐẦU DÒ NHIỆT ĐỘ
Beschreibung
iTHERM ModuLine TM131
(TM131-AABBWAJ1BX1AGBB3CA1AA1+NQ)
AA Approval: Non-hazardous area
B Thermowell: Thermometer with thermowell, continuous,
similar DIN43772 Form 2 G/F , 3 G/F
B Thermometer Design: Lagging, DIN43772
form 2G, 2F, 3G, 3F
WA Process/Thermowell Connection; Material: Flange DN25
PN40 B1 EN1092-1; PTFE >316Ti
J1 Thermowell Diameter; Material: 11x2mm; 316Ti+15mm
PTFE (TL=U+15mm)
B Tip Shape: Straight (DIN 43772 form 2/2G/2F)
X1 Immersion Length U: 500 mm ..... mm (=<1000 mm)
A Removable Neck Length E: 0mm, w/o neck
G Lagging Length T: 80 mm
B Sensor Type; Measuring Range; Material: 1x Pt100 WW;
-200...+600oC; 316L
B Sensor Standard; Classification: IEC60751; class A, 3-wire
3C Electrical Connection: 4-20mA HART, 2-channel TMT82,
head transmitter DIN B
A1 Terminal Head,Material,Protection Class: TA30A comfort flip
cover; Alu; IP66/68
A Cable Entry Terminal Head: 1x M20x1.5 female thread
A1 Device Model: 1
NQ>>Accessory Mounted: 1x cable gland Polyamide
Details: Low range value: 0 °C
Upper range value: 600 °C
dual-sensor configuration: PV = CH1; CH2 not